TY - JOUR N2 - The error reduction technique, based on inverse transformation, for a shunt active resistance measurement using an ammeter and voltmeter is considered. When computing a corrected reading only multiplicative operations on two measurement results are used, namely squaring and division. The proposed method allows to increase re-sistance measurement accuracy by about two orders of magnitude what has been validated by both theoretical and experimental outcomes. L1 - http://journals.pan.pl/Content/89811/PDF/Journal10178-VolumeXVIII%20Issue3_14paper.pdf L2 - http://journals.pan.pl/Content/89811 PY - 2011 IS - No 3 EP - 490 DO - 10.2478/v10178-011-0014-x KW - bias KW - error reduction technique KW - shunt ohmic resistance KW - indirect measurement A1 - Muravyov, Sergey A1 - Zlygosteva, Galina A1 - Borikov, Valeriy PB - Polish Academy of Sciences Committee on Metrology and Scientific Instrumentation DA - 2011 T1 - Multiplicative Method for Reduction of Bias in Indirect Digital Measurement Result SP - 481 UR - http://journals.pan.pl/dlibra/publication/edition/89811 T2 - Metrology and Measurement Systems ER -