TY - JOUR N2 - This paper describes a new and efficient method for quantifying and detection of the source of distortion caused by a single customer in a case when many other customers exist in a power grid. It is based on measuring distortion power, a component of apparent power that only exists with a nonlinear load. Different definitions for distortion power calculation are investigated. All these definitions show without doubt that the proposed method is feasible. Moreover, this method allows to develop fair and reliable billing schemes for controlling harmonic pollution. Measurement and simulation results confirm the effectiveness and applicability of the method. The proposed solution is suitable for software/hardware upgrade of existing electronic power-meters. L1 - http://journals.pan.pl/Content/90211/PDF/Journal10178-VolumeXXI%20Issue1_01.pdf L2 - http://journals.pan.pl/Content/90211 PY - 2014 IS - No 1 EP - 14 DO - 10.2478/mms-2014-0001 KW - distortion power KW - harmonic pollution source detection KW - power meter A1 - Stevanović, Dejan A1 - Petković, Predrag PB - Polish Academy of Sciences Committee on Metrology and Scientific Instrumentation DA - 2014 T1 - A SINGLE-POINT METHOD BASED ON DISTORTION POWER FOR THE DETECTION OF HARMONIC SOURCES IN A POWER SYSTEM SP - 3 UR - http://journals.pan.pl/dlibra/publication/edition/90211 T2 - Metrology and Measurement Systems ER -