Abstrakt

<jats:title>Abstract</jats:title> <jats:p> In the paper, analysis of multi-region fuzzy logic controller with local PID controllers for steam generator of pressurized water reactor (PWR) working in wide range of thermal power changes is presented. The U-tube steam generator has a nonlinear dynamics depending on thermal power transferred from coolant of the primary loop of the PWR plant. Control of water level in the steam generator conducted by a traditional PID controller which is designed for nominal power level of the nuclear reactor operates insufficiently well in wide range of operational conditions, especially at the low thermal power level. Thus the steam generator is often controlled manually by operators. Incorrect water level in the steam generator may lead to accidental shutdown of the nuclear reactor and consequently financial losses. In the paper a comparison of proposed multi region fuzzy logic controller and traditional PID controllers designed only for nominal condition is presented. The gains of the local PID controllers have been derived by solving appropriate optimization tasks with the cost function in a form of integrated squared error (ISE) criterion. In both cases, a model of steam generator which is readily available in literature was used for control algorithms synthesis purposes. The proposed multi-region fuzzy logic controller and traditional PID controller were subjected to broad-based simulation tests in rapid prototyping software - Matlab/Simulink. These tests proved the advantage of multi-region fuzzy logic controller with local PID controllers over its traditional counterpart.</jats:p>

Wydawca

Committee of Automatic Control and Robotics PAS

Data

2015[2015.01.01 AD - 2015.12.31 AD]

Identyfikator

ISSN 1230-2384

Referencje

Ansarifar (2012), Adaptive estimator - based dynamic sliding mode control for the water level of nuclear steam generators Progress in, Nuclear Energy, 56, 61, doi.org/10.1016/j.pnucene.2011.12.008 ; Banavar (1996), Robust controller design for a nuclear power plant using H optimization of the th on Decision and Control, Proc IEEE Conf, 4, 4474. ; Kim (1999), A gain - scheduled control to nuclear steam generator water level of, Annals Nuclear Energy, 26, 905, doi.org/10.1016/S0306-4549(98)00098-X ; Habibiya (2004), n eshi and A fuzzy - gain - scheduled neural controller for nuclear steam generators of, Annals Nuclear Energy, 31, 1765, doi.org/10.1016/j.anucene.2004.03.014 ; Fakhrazari (2008), Adaptive critic - based neurofuzzy controller for the steam generator water level on Nuclear, IEEE Trans Science, 55, 1678, doi.org/10.1109/TNS.2008.924058 ; Yu Cheng (2011), A new control strategy based on fuzzy - PID and water mass inventory for Nuclear Steam Generators Conf on Machine Learning and, Int Cybernetics, 1151. ; Gee Yong Park (1995), Application of a fuzzy learning algorithm to nuclear steam generator level control of, Annals Nuclear Energy, 22, 135, doi.org/10.1016/0306-4549(94)00052-G ; Munasinghe (2005), Min and Ju Adaptive neurofuzzy controller to regulate UTSG water level in nuclear power plants on Nuclear, IEEE Trans Science, 52, 421, doi.org/10.1109/TNS.2004.842723 ; Irving (1980), Adaptive control of non - minimum phase systems Application to the steam generator water level control th on Decision and Control , including The Symp on Adaptive Processes, IEEE Conf, 19, 274. ; Kothare (1997), Linear parameter varying model predictive control for steam generator level control Computers Supplement, Chemical Engineering, 21, 861. ; Hu (2008), Multi - model predictive control method for nuclear steam generator water level and, Energy Conversion Management, 49, 1167, doi.org/10.1016/j.enconman.2007.09.006

DOI

10.1515/acsc-2015-0028

×