Abstract

When a single line-to-ground fault occurs in the ungrounded distribution system, the steady-state fault current is relatively small for fault analysis and the transient fault current is observable, which can be used for faulted feeder identification and location. The principal frequency component retains most of the characteristics of the transient current. The principal frequency is related to the distance from the fault point to the substation and can be used for fault location. This paper analyzes the sequence network model of a single line-to-ground fault in the distribution network, and gives a method for principal frequency calculation. Depending on the characteristics of the maximum amplitude of the principal frequency component of the faulted feeder, the method of faulted feeder identification is given. Based on the complementary characteristics of the phase angle of the principal frequency component of the fault current and the phase angle at the substation bus, the faulted section location is carried out. MATLAB simulation is used to verify the effectiveness of the faulted feeder identification and location method.