The paper presents results of investigation of microstructure and micro-hardness for material of ZnO varistors applied to 110 kV surge arrester and surge arrester counter. The research combined two pairs of varistors, each consisted of one varistor subjected before to operation, while the other one was brand new unit and constituted a reference. All varistors were made of the same material by the reputable manufacture. The tests revealed a different degree of the material degradation for varistors subjected before to operation. This also refers to different degradation mechanism observed for the material of these varistors, if typical effects of degradation of aged ZnO varistors were considered as a reference. Physical state of spinel in the microstructure had a significant impact on the material degradation, however a considerable loosening of the microstructure associated with bismuth oxide was observed too. It was surprising, since the precipitates of the bismuth oxide phase most often showed very good binding to the ZnO matrix and high resistance to associated electrical, thermal and mechanical effects. The degradation effects in the ZnO matrix proved to be limited only.
The paper presents the test results for the microstructure of ZnO varistors comprising high voltage gapless surge arresters. The tests were performed on varistors produced in different periods and by various manufacturers. The research was inspired by different characteristics of changes in values of current flowing through surge arresters as a function of changes in values of system voltage in a 220 kV substation, and the temperature in a multi-year cycle. Furthermore, the effects of varistor microstructure degradation following a failure of an unsealed surge arrester were investigated. The results provided the grounds for assessment of ZnO varistor microstructure parameters in terms of their durability and resistance to degradation processes.
The paper presents a concept of an active filter with energy storage. This solution can be used for the compensation of momentary one phase high power loads with discontinued power consumption (e.g. spot welding machines). Apart from the typical filtering capabilities, the system’s task is also the continuity of the input power from the feeder line and limiting its fluctuation. The proposed by the author’s solution can produce measurable economic benefits by reducing the rated power necessary to energize periodically operating loads and improving the indicators of electrical energy quality. The developed method of active power surges compensation enables a flexible approach to requirements concerning the rated power of the point to which the periodically operating loads with high peak current value are connected. The tests were conducted on a simulation model specially developed in Matlab & Simulink environment, proving high effectiveness of the presented solution.
The paper presents investigations of microstructure of varistors of damaged surge arrester counters. A similar ZnO varistor, not subjected before to operation, was a point of reference in this research. The results of investigations of the ZnO varistors show an untypical phase composition of their material, which was characterized by unsatisfying homogeneity and cohesion. The degradation processes of varistor material in the subsequent stages were recognized and described. A harmful impact of humidity inside the untight surge arrester counter on its operation and its ZnO varistors was proved. Some conclusions being the result of the operation checking of surge arrester counters were presented too.
This paper investigated the problems and impacts of transient flow in pipeline systems due to pump power failure. The impact of different protection devices was presented to assure surge protection for the pipeline system. A model via Bent-ley HAMMER V8.0 Edition was employed to analyse and simulate hydraulic transients in the pipeline system, and protec-tion alternatives were studied.
Surge protection included using only an air vessel, using an air vessel and two surge tanks, and employing five air ves-sels and vacuum breaker. The obtained results for pressures, heads, and cavitation along the pipeline system were graph-ically presented for various operating conditions. Using five air vessels with vacuum breaker valve as surge protection proved to be more effective and economical against pump power failure.
Changing the flow density did not have a significant impact on the pressures.
For protection with an air vessel; it was concluded that the value 40% of the original diameter for inlet pipe diameter of air vessel, and the value of 2/3 of original pipe diameter were critical values for the transient pressures. Cast iron pipes proved to be the best pipe material for all studied volumes of the air vessel.
For protection with an air vessel and two surge tanks; as the inlet pipe diameters increased the maximum pressures in-creased and the minimum pressures decreased.
Regression analyses were performed obtaining equations to predict the pressures according to the inlet pipe diameter, the area of surge tank, and the pipe diameter.